Open Discharge System
Table of Contents
| Standard of Practice | Explanation |
10. Open Discharge System |
See Pg. 207, Fig. Typical OD 1 in Appendix "B" |
10.1. Design Standards |
|
| 10.1.1. A system designed to discharge effluent to the surface of the ground shall contain the effluent on the property. | See Pg. 160, Open Discharge in Appendix "B" |
| 10.1.2. An open discharge system shall be designed to minimize effluent pooling on the ground surface during nonfreezing temperatures. | |
|
10.1.3. At the point of discharge of effluent to the surface, the soil the effluent is discharged onto shall be protected from erosion. Intent: The design of the point of discharge must include landscaping to disperse the effluent allowing the quick evaporation and absorption of the effluent, and must protect the soil from erosion. |
See Pg. 210, Fig. OD 1 in Appendix "B" See Pg. 211, Fig. OD 2 in Appendix "B" See Pg. 211, Fig. OD 3 in Appendix "B" |
10.2. Installation Standards |
|
10.2.1. An effluent discharge to the ground surface shall not be located within
|
See Pg. 38, Article 7.1.6. for Vertical Separation Requirements. See Pg. 178, Fig Vertical Separation in Appendix "B" |
| 10.2.2. The soil receiving the effluent from an open discharge system shall have a percolation rate slower than 5 minutes per inch.
Intent: The soil the effluent is discharged onto must have a percolation rate slower than 5 minutes per inch as required in Article 7.1.5. The soil percolation rate may exceed 60 minutes per inch. Vertical separation distances of Article 7.1.6. must also be met. |
See Pg. 38, Article 7.1.5 |
10.3 Requirements for Materials |
|
| 10.3.1. Piping used in an open discharge system shall be certified for that use or comply with Appendix A Piping Materials list for a pressure effluent line. |
See Pg. 93, Table A.5.A in Appendix "A" |



